09.07.02 NYCY 0,6/1 kV

Application

Power cable for use in generating plants, industrial facilities, switching stations, in local networks and power supply industry. Use predominantly for laying underground, indoor- and outdoor use, cable channels and in water when increased mechanical protection resp. contact protection in case of failure is required.

Special Features

  • 0,6/1 kV operating voltage, 4 kV testing voltage
  • UV-resistant
  • no hood termination necessary when laying in dry rooms
  • use of concentric conductor as shield, neutral conductor or earth conductor is permitted but not as outer conductor
  • free from lacquer damaging substances and silicone (during production)

Remarks

  • conform to RoHS
  • conform to 2006/95/EC-Guideline CE
  • with blue outer sheath for intrinsically safe facilities available upon request
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Structure & Specifications

conductor_material bare copper conductor
conductor_class acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
insulation_material PVC
wire_identification single core black; multi core acc. to VDE 0207 part 4
twisting multi core stranded in layers
shielding_total concentric conductor of blank round copper wires
innersheath_material filler sheath
outersheath_material PVC
sheath_color black
voltage_nominal Uo/U: 0,6/1 kV
voltage_test 4 kV
resistance_conductor at +20 °C acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
carrying_capacity acc. to DIN VDE, see Technical Guidelines
bending_radius_smallest_fixed single core: 15 x d ; multi core: 12 x d
operating_temperature_fixed -40 °C / +70 °C
operating_temperature_moving - 5 °C / +50 °C
conductor_temperature_max + 70 °C in operation; +160 °C in case of short-circuit
fire_behaviour acc. to VDE 0472-804-B and IEC 60332-1
standard acc. to DIN VDE 0271 and IEC 60502
approbation VDE

Downlaod Datasheet Download certificate

To top