Power cable for use in generating plants, industrial facilities, switching stations, in local networks and power supply industry. Use predominantly for laying underground, indoor- and outdoor use, cable channels and in water when increased mechanical protection resp. contact protection in case of failure is required.
Special Features
0,6/1 kV operating voltage, 4 kV testing voltage
UV-resistant
no hood termination necessary when laying in dry rooms
use of concentric conductor as shield, neutral conductor or earth conductor is permitted but not as outer conductor
free from lacquer damaging substances and silicone (during production)
Remarks
conform to RoHS
conform to 2006/95/EC-Guideline CE
with blue outer sheath for intrinsically safe facilities available upon request
We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Structure & Specifications
conductor_material
bare copper conductor
conductor_class
acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
insulation_material
PVC
wire_identification
single core black; multi core acc. to VDE 0207 part 4
twisting
multi core stranded in layers
shielding_total
concentric conductor of blank round copper wires
innersheath_material
filler sheath
outersheath_material
PVC
sheath_color
black
voltage_nominal
Uo/U: 0,6/1 kV
voltage_test
4 kV
resistance_conductor
at +20 °C acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
carrying_capacity
acc. to DIN VDE, see Technical Guidelines
bending_radius_smallest_fixed
single core: 15 x d ; multi core: 12 x d
operating_temperature_fixed
-40 °C / +70 °C
operating_temperature_moving
- 5 °C / +50 °C
conductor_temperature_max
+ 70 °C in operation; +160 °C in case of short-circuit