05.01.34 KAWEFLEX® SERVO 9YSL(St)CY-J 0,6/1kV EMC UL/CSA

Application

Power, control and connecting cable for drive systems with frequency converter technology, for fixed laying and casually movement without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms.   Versions with black outer sheath (DB - direct burial) are additionally suitable for outdoor use and for direct burial.     

Special Features

  • largely resistant to acids, bases and specified types of oil
  • max. perm. current carrying capacity at 30 °C ambient temperature
  • low operating capacity, low coupling resistance
  • black version: UV-resistant, cold flexible, outdoor and direct burial use PVC outer jacket
  • enables trouble-free operation of frequency converters through optimum EMC compliant shielding
  • low capacitance enables longer cable lengths between motor and frequency converter

Remarks

  • conform to RoHS, conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • Outdoor use and direct burial installation are not covered by UL/CSA approval.
  • Special versions are manufactured on request.

Structure & Specifications

conductor material bare copper strand
conductor class acc. to IEC 60228 cl. 5
core material PP
core identification acc. to DIN VDE 0293-308 coloured cores with GNYE
stranding 4-core version: cores stranded in one layer | 3+3-core version: cores stranded concentrically, protective conductor divided into three, positioned in the crotches
shield alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned
outer sheath PVC
sheath colour transparent, DB-version: black
rated voltage acc. to IEC: 0,6/1 kV, acc. to UL: 1.000 V - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V
testing voltage 4 kV
conductor resistance acc. to IEC 60228 cl. 5
insulation resistance min. 200 MΩ x km
current carrying capacity look at the table on the right side
capacity look at the table on the right side
min. bending radius fixed 4 x d
min. bending radius moved 15 x d
operat. temp. fixed min/max transparent: -40°C / +80°C; black: IEC: -40°C / +90°C, UL/CSA: -40°C / +80°C
operat. temp. moved min/max transparent: - 5°C / +80°C; black: IEC: - 5°C / +90°C, UL/CSA: - 5°C / +80°C
temp. at conductor + 90 °C in operation; +250 °C in case of short-circuit
burning behavior self-extinguishing & flame-retardant acc.to IEC 60332-1, FT1, VW-1
approvals UL/CSA - cURus 1.000V, 80°C

Download datasheet

To top